Automation Inc. EP-1 Bedienungsanleitung Seite 5

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 7
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 4
Siemens Energy & Automation, Inc.
Bellefontaine, OH 43311 U.S.A.
Page 5 of 7
Hazardous voltage.
Will cause death or serious
injury.
Turn off and lock out all power supplying
the circuit breaker prior to cover(s) removal
or while cover(s) are removed and when
installing any internal or external accessory.
Replace the cover(s) and shield(s) before
power supplying this device is turned on.
Installation:
1. When the factory-installed ACCESS communications option is present, the EPSB expansion plug is already wired
to the breaker and secondary control terminals. Connect an MTCSB cables spade lugs to the appropriate SB
breakers secondary terminals (LB9, 10, 11, & 12) then to one of eight communication inputs on the MTA.
2. If ZSI functionality is additionally required, per the sites coordination study, configure the expansion plugs
DIP switches for Short Time and/or Ground Fault ZSI per the expansion plugs Information and Instruction
Sheet. Configure the MTA to identify the zones for each breaker, per the sites coordination study and the
MTAs instruction sheet.
3. If multiple MTs are used, the Com terminal from the first MTs SEABus Out port must be connected to the
Com terminal of the next MTs SEABus In port on each MT being used.
4. If ZSI is not required, set the expansion plugs DIP switches to NO ZONE (0000), the MTAs Device Configu-
ration DIP switches to NO ZONE (00) and the Device Type MTAs DIP switch to MCCB/ICCB (0001).
5. Connect RS-485 twisted pair communication cable to the MTAs A(+) and B(-) terminals. Connect only one
end of the cables shield to the MTs GND terminal. Configure the ACCESS system network, per Installing the
ACCESS System manual. An Isolated Multidrop Converter may be installed as an option. See figure 1 for
system connection diagram.
2. SB-EC Trip unit
Since the SB-EC Trip Unit has direct communications with an ACCESS network, no intermediate devices are
required unless ZSI functionality is required.
If ZSI is required, connect as per above using an MTA if type TL SB breaker trip units or Sensitrip MCCB trip
units are part of the overall system and both ACCESS communications and ZSI are required
Any application requiring only ZSI requires an MTZ configured as above.
If multiple MTs are used for ZSI functionality, the Com terminal from the first MTs SEABus Out port must be
connected to the Com terminal of the next MTs SEABus In port on each MT being used.
As referenced in the SB-EC Trip Unit Information and Instruction Manual, the trip units ACCESS communication
lines are located on the breakers secondary control terminals <LB5> to RS485(+), <LB6> to RS-485(-), and
<LB7> to Shield/Common. Refer to figure 1 for system connection diagram.
Installing Sensitrip
TM
and SB Electronic Trip Units In Zone
Selective Interlocking or ACCESS
TM
Communications Systems
Seitenansicht 4
1 2 3 4 5 6 7

Kommentare zu diesen Handbüchern

Keine Kommentare